Verification of Conformity — UL 1741 PCS CRD and UL 3141

Report Number: 80266993VOC | Project Number: 80266993 | Master Contract: 302773

Issued by: CSA Group, Suite 138 - 13888 Wireless Way, Richmond, BC, V6V 0A3

Date of tests: 2025-07-11 to 2025-08-14 | Signed: Peter Lim, Power and Energy | August 25, 2025

Summary

This report provides a detailed assessment of the compliance of the Lunar System with UL 1741-CRD PCS and UL 3141-Issue 1 standards, focusing on the Power Control System (PCS) integrated into these products.

Products Tested

Lunar ESS (LE-ESS-20KWH, LE-ESS-15KWH, L2-ESS-15KWH, L2-ESS-20KWH, L2-ESS-25KWH, L2-ESS-30KWH), Lunar Inverter (10-005025), Lunar MSAC (LE-MSAC-01), ConnectDER MSA (V-1-A-X).

Applicable Standards

  • UL 1741, 3rd Edition (September 28, 2021, Revision May 19, 2023) — PCS Certification Requirement Decision Date: 2023-04-08, Revised: 2024-01-18

  • UL 3141, Issue Number 1 (January 11, 2024)

System Description

The Lunar Battery system (Inverter + Battery Block) combined with the Lunar MSAC and ConnectDER MSA is certified for UL 1741 PCS CRD and UL 3141 Issue 1, with the PCS controller integrated within the Lunar Inverter. Open-loop response time is less than 2 seconds. Maximum PCS Controlled Current: 200A (Bridge & Main Panel).

PCS settings are not mandatory for installation, but can be configured to facilitate NEC compliance and/or utility interconnection requirements.

PCS Functionalities

  1. Power Import Limiting (PIL)

  2. Power Export Limiting (PEL)

  3. Busbar Overload Control (BBOC)

  4. Feeder Conductor Overload Control (FCOC)

ESS Operating Modes — Response Times

PCS Mode

Description

Max OLRT

Avg OLRT

Unrestricted Mode

Battery charges from PV and grid; battery and PV can export to grid

61.535 ms

5.69 ms

Export Only Mode

Battery charges from PV only; battery and PV can export to grid

753.598 ms

11.19 ms

Import Only Mode

Battery charges from PV and grid; only PV can export to grid

309.262 ms

10.01 ms

No Exchange Mode

Battery charges from PV only; only PV can export to grid

226.679 ms

12.08 ms

Test Results Summary

UL 1741 CRD

UL 3141

Test

Result

203.5

8.3

Step Change in Load Test

PASS

203.6

8.4

Step Change in Generation Test

PASS

204.1.1

8.6.2

Export Limiting from all sources to EPS

PASS

204.1.1

8.6.2

Import Limiting from area EPS

PASS

204.4

8.6.5

Export Limiting from ESS

PASS

204.5

8.6.6

Import Limiting to ESS

PASS

205.5

8.7

Startup/Self check Abnormal Tests

PASS

205.7

8.7

Operating Abnormal Tests

PASS

Conclusion

The Lunar PCS system has demonstrated full compliance with UL 1741 PCS CRD and UL 3141 Issue 1, reflecting its capability to perform critical power control functions reliably and safely.

Important Note: The Lunar PCS is supplemental protection. All PCS-controlled busbars or conductors must also be protected with suitably rated overcurrent devices. PCS settings may be used for NEC Article 690, 705, 706, 750, 220, 710 calculations as supplemental protection, but overcurrent protective devices remain essential per NFPA 70.